[rank_math_breadcrumb]

Alternator A.R.K4F

A.R.K4F Alternator – Brushless, High-Efficiency, and PMG-Excited Industrial Alternator

The A.R.K4F alternator, engineered by Arken Power Solutions, is a three-phase, brushless synchronous alternator with a PMG excitation system, ensuring exceptional voltage stability and transient performance. With ±1% voltage regulation and less than 5% total harmonic distortion (THD), it provides clean, reliable power output for both prime and standby applications. Built with Class H insulation, IP23 protection, and a durable steel frame, it offers high efficiency up to 94.1% and long operational life. Certified under IEC60034, BS5000, NEMA MG1-22, CSA C22.2-100, and ISO9001, the A.R.K4F alternator is ideal for industrial, rental, mobile, and telecom generator systems.

Alternator Model

A.R.K4F

50Hz (kVA)

380

60Hz (kVA)

456
Control SystemSELF EXCITED
A.V.R.MX341 WITH PMG
Voltage Regulation ± 1.0 %
Sustained Short Circuit>300% OF RATED CURRENT
Rated Power Factor0.8

Electrical Performance

  • Type: Three-phase, brushless, self-excited synchronous alternator with PMG excitation

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 380/220V – 480/277V (reconnectable; star, delta, or parallel configurations)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5.0% (balanced load), <1.5% (no load)

  • Efficiency: Up to 94.1% at full load

  • Sustained Short Circuit Current: >300% rated current for 10 seconds

  • Overload Capacity: 110% for one hour in a six-hour cycle

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Short Circuit Ratio (1/Xd): 0.09

  • Reactances (per-unit at rated kVA):

    • Xd (Synchronous): 2.17–3.21

    • X’d (Transient): 0.14–0.18

    • X’’d (Subtransient): 0.09–0.13

    • Xq (Quadrature): 1.66–2.84

    • X’’q (Quadrature Subtransient): 0.25–0.42

    • X₂ (Negative Sequence): 0.16–0.28

    • X₀ (Zero Sequence): 0.06–0.10

  • Time Constants:

    • Transient (T’d): 0.08 s

    • Subtransient (T’’d): 0.019 s

    • Armature (Ta): 0.018 s

    • Open Circuit Field (T’do): 1.7 s

  • Short-Circuit Capability: 300% of rated current for 10 seconds

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23

  • Cooling System: Self-ventilated air flow (0.486 m³/s @50Hz, 0.580 m³/s @60Hz)

  • Frame Material: Rigid steel frame with cast aluminum front and rear covers

  • Winding: Double-layer stator winding, 2/3 pitch design to reduce harmonic distortion

  • Rotor: Damped rotor with dynamic balancing per BS6861

  • Bearings:

    • Drive End: 6317 (sealed-for-life ball bearing)

    • Non-Drive End: 6314 (sealed-for-life ball bearing)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 leads, reconnectable for multiple configurations

  • Moment of Inertia (WR²):

    • Single Bearing: 5.43 kg·m²

    • Double Bearing: 5.23 kg·m²

  • Weight:

    • Complete Alternator: 1160 kg

    • Rotor: 440–463 kg

    • Stator: 535 kg

  • Shipping Weight: 1775–1780 kg

  • Packing Dimensions: 155×87×107 cm (50Hz), 156×87×107 cm (60Hz)

Regulation & Control

  • Excitation System: PMG excitation with AVR

  • AVR Model: MX341 (standard), optional SX460, SX440, AS440, MX321

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR dependent)

  • RFI Suppression: Complies with BS EN 61000-6-2 and BS EN 61000-6-4, VDE 0875G/N

  • Low-Speed Voltage Drop Protection: Standard

  • Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Noise & Vibration: Balanced to BS6861 standards

  • Cooling Air Requirement: 0.486 m³/s @50Hz, 0.580 m³/s @60Hz

Performance Summary

  • Voltage Dip (Transient Load): ≤25% at 0.8 power factor

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% of rated current

  • Efficiency Range: 93.4–94.1% across load range

  • Applications: Prime power, standby, telecom, mobile lighting towers, railway, refrigeration, and rental generator systems

Datasheet

Related Products