[rank_math_breadcrumb]

Alternator PRO28L G/4

Linz Electric PRO28L G/4 Alternator – 400 kVA Three-Phase Brushless Synchronous Alternator

The PRO28L G/4 alternator by Linz Electric is a high-performance three-phase, 4-pole brushless synchronous alternator delivering 400 kVA at 50 Hz and 480 kVA at 60 Hz. Designed for industrial generator applications, it features electronic AVR voltage regulation, Class H insulation, IP23 protection, and low harmonic distortion, ensuring reliable and stable electrical output even under demanding operating conditions.

Alternator Model

PRO28L G/4

50Hz (kVA)

400

60Hz (kVA)

480
Control Systemself-excited
A.V.R.HVR11-HVR30
Voltage Regulation± 1 %
Sustained Short Circuit> 250 % of rated current
Rated Power Factor0,8
  • General Characteristics:

    • Three-phase, 4-pole synchronous alternator

    • Brushless, self-excited excitation system

    • Electronic voltage regulation (AVR)

    • Rated speeds: 1500 rpm (50 Hz) / 1800 rpm (60 Hz)

    • Cooling system: Self-ventilated

    • Protection degree: IP23

    • Insulation class: H

    • Standards: EN 60034-1, IEC 60034-1, ISO 8528-3

  • Electrical Specifications:

    Rated Power (50 Hz): 400 kVA

    Rated Power (60 Hz): 480 kVA

    • Rated voltage: 400/230 V (50 Hz) / 480/277 V (60 Hz)

    • Rated current: 289.0 A

    • Power factor: 0.8

    • Frequency: 50 / 60 Hz

    • Phase: Three-phase

    • Efficiency:

    92.3% at 50 Hz

    93.3% at 60 Hz

    • Transient reactance X’’d: 0.058 p.u.

    • Harmonic distortion (THD): < 5%

    • Winding pitch: 2/3

  • Excitation & Regulation:

    • Brushless excitation with auxiliary winding

    • AVR installed inside terminal box

    • 12-lead reconnectable stator winding (various voltage configurations)

    • Stable voltage under load variations

  • Mechanical Specifications:

    • Frame size: 28

    • Dimensions:

    – Length (L): 973 mm

    – Height (H): 690 mm

    – Width (W): 540 mm

    • Shaft diameter: 55 mm

    • Total weight: 396 kg

    • Cooling system: Forced by shaft-mounted fan

    • Mounting: Suitable for single-bearing generator coupling

  • Operational Performance:

    • Stable voltage recovery during sudden load steps

    • High electrical efficiency improves fuel performance of gensets

    • Suitable for continuous and standby duty

    • Works with resistive, inductive, and nonlinear loads

  • Applications:

    • Industrial and commercial generator sets

    • Backup/emergency power plants

    • Rental and construction gensets

    • Telecommunications, utilities, infrastructure systems