[rank_math_breadcrumb]

Sdec Diesel Generator ARK-S 100 N5

ARK-S 100 N5 Diesel Generator – Efficient, Reliable, and Industrial-Grade Power Solution

The ARK-S 100 N5 diesel generator, developed by Arken Power Solutions, delivers 83 kVA prime and 90.8 kVA standby power, providing reliable, fuel-efficient, and durable energy for industrial, commercial, and residential applications. Powered by the SDEC SC4H115D2 4-cylinder, turbocharged, water-cooled engine, it ensures exceptional performance, long service life, and smooth operation under varying load conditions. Its NEKRA ARK 224G alternator with electronic AVR guarantees ±1% voltage regulation and <5% THD, providing clean, stable, and consistent power output. Built in compliance with ISO 8528 and ISO 3046 standards, the ARK-S 100 N5 operates quietly at 71.9 dBA, features a corrosion-resistant canopy, and comes with a 2-year or 1000-hour warranty, making it a dependable and efficient power generation solution for both continuous and standby use.

Power Prime (kVA / kW)

83 / 66,4

Power Standby (kVA / kW)

90,8 / 72,6

Speed (r.p.m)

1500

Standard Voltage

400/230VAC

Power Factor(Cos Phi)

0,8
BrandSdec
Güç kW PRP78
ModelSC4H115D2
N° of Cylinders / Valves4/16
Engine Type4 Stroke
Displacement [lt]4,3
AspirationTurbocharger
Bore[mm] x Stroke[mm]105X124
Compression Ratio17,3:1
Air FilterReplaceable Element
Cooling MethodWater Cooled (water + %50 antifreeze)
Total Coolant Capacity (lt)19,3
Governor TypeElectronic
Electrical System24VDC
Battery Charger Current55A
Oil Capacity [lt]13
Exhaust Gas Flow PRP [m3/min]14,1
Exhaust Gas Temp. [°C]600
Air Flow PRP [m3/min]6,2
Cooling Air Flow PRP [m3/min]141
Starter Power (kW)4,5kW
Standard Battery Voltage [V]24VDC
Standard Battery Capacity2x60Ah
Standard Battery TypeMaintenance-Free Lead Acid
BrandNekra
ModelARK 224G
Voltage400 /230 VAC
Number of Phase3
Power Factor0,8
Number of Poles4
Connection TypeStar
BearingSingle

ENGINE
Arken Jenerator provides industrial diesel engines that meet ISO 8528, ISO 3046 specifications; heavy duty type; oil, air or water-cooled depending on the requirements; low fuel consumption; with mechanical and/or electronical type of governor mounted on fuel pump to ensure precise speed adjustment and regulation; with oil, fuel and air filter system based on diesel type; oil and fuel designed for heavy operational conditions in order to make sure the unit lasts a long time with high performance; 4-stroke; direct injection with all the limit and level sensors required for diesel protection. The diesel engine is supplied with all the necessary equipment for safe operation. Only engines designed for standby are not included in the production portfolio.

ALTERNATOR
Arken Jenerator uses original European brand alternators for its gensets, that complies with all international certificates, IEC 60034-1, ISO8528-3, EN50511, BS4999-5000 VDE 0530, depending on their power and requirements. The alternators, that has high efficiency and high performance for all conditions, have all the quality certificates and comply with world standards.

COOLING SYSTEM
Arken Jenerator chooses its radiators from the original selection or from approved vendor list of its engine on boards for the purpose of usability, spare part availability, high performance and maximum efficiency. 55C remote type radiators are appliible.

FRAME
Arken Jenerator manufactures its own chassis based on international standards for all generator sets. The frames are designed and manufactured to provide high strength from the inside of the plate panel or profile to the vibration and stresses.

FUEL TANK
Arken Jenerator uses an in-chassis daily fuel tank in generator sets up to 800kVA. Larger power sets are supplied with an external stand-type fuel tank. Fuel tanks can be manufactured from plate steel or other suitable materials in accordance with the relevant standards. Arken fuel tanks mainly include:

  • Fuel fill point and cap
  • Tank vents
  • Fuel outlet valve
  • Fuel return connection
  • Tank drain plug
  • Sludge, etc. accumulation section
  • Transparent fuel level gauge
  • Floating level switch / Automatic Fill (Optional)

CANOPY
To provide sound isolation (ISO8528-10:1998) and to protect the generator from corrosive effects of external weather conditions, cabinets or containers are used depending on the size of the generator or the degree of sound intensity. Even low noise level is targeted principally, the cabins are designed in order to deliver stated power, in addition to the conditions set by ISO3046 and ISO8528, according to the tropical climate at 50C ambient temperatures, relative humidity of 30% at sea level is designed to deliver the declared power. Cabs come with a compact construction, low height, low sound level, easy access to the engine-alternator and control panel, lifting at two point, exhaust silencer stored in the cabin for safety and non-corrosion protection, and with ease of disassembly.

DOCUMENTATION
Maintenance and operation manual, Engine and alternator manuals, Controller booklet, Warranty sheet, Electrical diagram.

WARRANTY
The warranty period begins from the date of the invoice of the item and runs upto 1 Year or 1000 hours.

Datasheet