Альтернатор A.R.K4E — бесщёточный высокоэффективный промышленный альтернатор
A.R.K4E обеспечивает стабильное напряжение и чистую генерацию энергии для промышленных, арендных и телекоммуникационных систем.
[rank_math_breadcrumb]
A.R.K4E обеспечивает стабильное напряжение и чистую генерацию энергии для промышленных, арендных и телекоммуникационных систем.
Electrical Performance
Type: Three-phase, brushless, self-excited synchronous alternator
Frequency: 50 / 60 Hz
Power Factor: 0.8
Voltage Range: 380/220V – 480/277V (configurable in star, delta, or parallel star)
Voltage Regulation: ±1.0%
Total Harmonic Distortion (THD): <5% (balanced load), <1.5% (no load)
Sustained Short Circuit Current: >300% of rated current for 10 seconds
Efficiency: Up to 94.3% at full load
Telephone Harmonic Factor (THF): <2%
Telephone Interference Factor (TIF): <50
Overload Capacity: 110% for one hour in a six-hour cycle
Reactances:
Xd: 2.79–3.33
X’d: 0.14–0.20
X’’d: 0.10–0.14
Xq: 2.01–2.80
X’’q: 0.25–0.39
Time Constants:
Transient (T’d): 0.08 s
Subtransient (T’’d): 0.019 s
Armature (Ta): 0.018 s
Short Circuit Ratio (1/Xd): 0.09 typical
Construction & Design
Insulation Class: H (125°C rise at 40°C ambient)
Protection: IP23
Cooling System: Self-ventilated airflow (0.486 m³/s @50Hz, 0.580 m³/s @60Hz)
Frame Structure: Steel frame with cast aluminum front and rear covers
Winding: Double-layer stator winding with 2/3 pitch to minimize harmonic distortion
Rotor: Damped rotor with high mechanical balance and low vibration
Bearings:
Drive End: 6317 (sealed-for-life ball bearing)
Non-Drive End: 6314 (sealed-for-life ball bearing)
Overspeed Capability: 120% of rated speed (2250 rpm)
Leads: 12 leads, reconnectable (star, delta, parallel)
Moment of Inertia (WR²): 4.63 kg·m² (single bearing), 4.43 kg·m² (double bearing)
Weight:
Complete Alternator: 1024–1030 kg
Stator: 470 kg
Rotor: 377–400 kg
Regulation & Control
Excitation System: Self-excited, brushless
AVR Models: SX460 (standard), SX440, AS440, MX341, MX321 (PMG optional)
Voltage Regulation Accuracy: ±1.0%
Parallel Operation: Supported (optional AVR required)
RFI Suppression: Complies with BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N
Low-Speed Voltage Drop Protection: Standard feature
Standards Compliance: IEC60034, BS5000, NEMA MG1-22, ISO8528-3
Certification: ISO9001 quality assurance
Environmental Parameters
Operating Temperature: –15°C to +40°C
Relative Humidity: Up to 95% (non-condensing)
Altitude: Up to 1000 m without derating
Noise and Vibration: Conforms to BS6861 mechanical balance standard
Performance Summary
Voltage Dip (Transient Load): ≤25% at 0.8 power factor
Recovery Time: <0.5 seconds
Locked Rotor Motor Starting: >300% rated current
Efficiency Range: 93.5–94.3% across load range
Applications: Prime power, standby, rental, telecom, mobile lighting towers, and refrigeration systems