Electrical Performance
Type: Three-phase, brushless, self-excited synchronous alternator
Frequency: 50 / 60 Hz
Power Factor: 0.8
Voltage Range: 190–480 V (configurable in star, delta, or parallel star)
Voltage Regulation: ±1.0%
Total Harmonic Distortion (THD): <5% (balanced load), <1.5% (no-load)
Sustained Short Circuit Current: >300% of rated current
Efficiency: 84.2–87.3% (depending on frequency and voltage)
Telephone Harmonic Factor (THF): <2%
Telephone Interference Factor (TIF): <50
Excitation System: Self-excited, AVR-controlled
AVR Models: SX460 (standard), SX440 / AS440 / MX341 / MX321 optional (PMG-compatible)
Short Circuit Ratio (1/Xd): 6.1 typical
Reactances (Per Unit, Saturated)
Xd (Synchronous): 1.53–2.16
X’d (Transient): 0.158–0.210
X’’d (Subtransient): 0.10–0.15
Xq (Quadrature): 0.77–1.09
X’’q (Quadrature Subtransient): 0.17–0.25
X₂ (Negative Sequence): 0.14–0.20
X₀ (Zero Sequence): 0.07–0.09
Leakage Reactance (XL): 0.06–0.09
Time Constants:
Transient (T’d): 0.022 s
Subtransient (T’’d): 0.005 s
Armature (Ta): 0.0065 s
Open Circuit Field (T’do): 0.4 s
Construction & Design
Insulation Class: H (125°C rise at 40°C ambient)
Protection: IP23 (optional IP44 with 5–10% derating)
Cooling: Self-ventilated air cooling
50 Hz: 0.095 m³/s (200 cfm)
60 Hz: 0.119 m³/s (250 cfm)
Frame: Steel frame with cast aluminum front and rear covers
Stator: Double-layer winding, 2/3 pitch eliminates triple harmonics
Rotor: Damped cage rotor, dynamically balanced to BS6861 standards
Bearings:
Drive End: 6309-2RS (ISO standard, sealed-for-life)
Non-Drive End: 6306-2RS (ISO standard, sealed-for-life)
Overspeed Capability: 120% of rated speed (2250 rpm)
Leads: 12 reconnectable leads (star, delta, or parallel star)
Stator Resistance: 0.25 Ω/phase (22°C, star connection)
Rotor Resistance: 0.74 Ω (22°C)
Rotor Inertia (WR²): 0.1909 kg·m²
Dimensions & Weight
Rotor Weight: 49.7–50.5 kg
Stator Weight: 55 kg
Complete Alternator Weight: 151–154 kg
Shipping Weight: 141–156 kg (crated)
Packing Dimensions: 84 × 59 × 75 cm
Regulation & Control
Excitation: Self-excited, AVR-controlled
AVR Models: SX460 (standard), SX440 / AS440 / MX341 / MX321 optional
Voltage Regulation Accuracy: ±1.0%
Parallel Operation: Supported (AVR-dependent)
RFI Suppression: BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N compliant
Standards Compliance: IEC60034, GB755, BS5000, VDE0530, NEMA MG1-22, CSA C22.2-100, AS1359
Certification: ISO9001 Quality Management System
Environmental Parameters
Operating Temperature: –15°C to +40°C
Relative Humidity: Up to 95% (non-condensing)
Altitude: Up to 1000 m without derating
Cooling Air Requirement: 0.095–0.119 m³/s
Noise & Vibration: Balanced per BS6861 mechanical standards
Performance Summary
Efficiency Range: 84–87.3%
Voltage Dip (Transient Load): ≤25% at 0.8 PF
Recovery Time: <0.5 seconds
Locked Rotor Motor Starting: >300% rated current
Applications: Prime power, standby, rental, telecom, mobile, lighting tower, refrigeration, and railway generator systems