A.R.K6D Alternator – PMG Excited, Brushless, and Industrial-Grade High-Efficiency Alternator

The A.R.K6D alternator, developed by Arken Power Solutions, is a robust three-phase, brushless synchronous alternator with PMG excitation and MX341 AVR control, ensuring superior voltage stability and excellent transient response. With ±1% voltage regulation and less than 5% THD, it provides clean, stable power suitable for industrial, telecom, rental, and standby generator applications. Built with Class H insulation, IP23 protection, and a rigid steel frame, the A.R.K6D combines mechanical durability with up to 95.6% efficiency, making it ideal for demanding power systems. Fully compliant with IEC60034, BS5000, NEMA MG1-22, CSA C22.2-100, and ISO9001, it offers reliability, long lifespan, and smooth operation even under harsh environmental conditions.

Alternator Model

ARK6D

50Hz (kVA)

940

60Hz (kVA)

1063
Control System SELF EXCITED
A.V.R. MX341 WITH PMG
Voltage Regulation ± 1.0 %
Sustained Short Circuit >300% OF RATED CURRENT
Rated Power Factor 0.8

Electrical Performance

  • Type: Three-phase, brushless, self-excited synchronous alternator with PMG excitation

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 380/220V – 480/277V (configurable in star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced load), <1.5% (no load)

  • Sustained Short Circuit Current: >300% rated current for 10 seconds

  • Efficiency: 94.5–95.6% depending on load and frequency

  • Overload Capacity: 110% for one hour in a six-hour period

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Short Circuit Ratio (1/Xd): 0.09 typical

  • Power Ratings (Winding 311):

    • 50 Hz: 830–1000 kVA (Efficiency 95.2–95.6%)

    • 60 Hz: 913–1219 kVA (Efficiency 94.5–95.4%)

  • Reactances (Per Unit at Rated kVA):

    • Xd (Synchronous): 2.70–3.37

    • X’d (Transient): 0.19–0.23

    • X’’d (Subtransient): 0.08–0.10

    • Xq (Quadrature): 1.77–3.13

    • X’’q (Quadrature Subtransient): 0.18–0.25

    • X₂ (Negative Sequence): 0.16–0.20

    • X₀ (Zero Sequence): 0.08–0.10

    • Leakage Reactance (XL): 0.02–0.03

  • Time Constants:

    • Transient (T’d): 0.18 s

    • Subtransient (T’’d): 0.025 s

    • Armature (Ta): 0.04 s

    • Open Circuit Field (T’do): 2.44 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with 5–10% power reduction)

  • Cooling: Self-ventilated air cooling

    • 50 Hz: 1.614 m³/s (3420 cfm)

    • 60 Hz: 1.961 m³/s (4156 cfm)

  • Frame: Rigid steel structure with cast aluminum front and rear covers

  • Stator: Double-layer winding, 2/3 pitch eliminates 3rd, 9th, and 15th harmonics

  • Rotor: Damped rotor dynamically balanced per BS6861 standards

  • Bearings:

    • Drive End: 6224 (ISO, sealed-for-life ball bearing)

    • Non-Drive End: 6317 (ISO, sealed-for-life ball bearing)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads (star, delta, or parallel star)

  • Inertia (WR²): 19.4965 kg·m² (2-bearing) / 20.0438 kg·m² (1-bearing)

  • Cooling Air Requirement: 1.614–1.961 m³/s

  • Winding Resistance:

    • Stator: 0.003 Ω/phase (22°C, star connection)

    • Rotor: 1.88 Ω (22°C)

Dimensions & Weight

  • Rotor Weight: 866–1010 kg

  • Stator Weight: 1010 kg

  • Complete Alternator Weight: 2117–2180 kg

  • Shipping Weight (Crated): 2145–2173 kg

  • Packing Dimensions: 183 × 92 × 140 cm

Regulation & Control

  • Excitation System: PMG excitation with brushless design

  • AVR Model: MX341 (standard), optional SX460, SX440, AS440, MX321

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR-dependent)

  • Protection Features:

    • Stator winding and bearing overheat protection

    • Anti-condensation heater (optional)

  • RFI Suppression: Complies with BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N

  • Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 1.614 m³/s (50Hz), 1.961 m³/s (60Hz)

  • Noise & Vibration: Balanced to BS6861 mechanical standards

Performance Summary

  • Efficiency Range: 94.5–95.6%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, rental, telecom, mobile, lighting tower, railway, and refrigeration generator systems