Альтернатор A.R.K5E — бесщёточный PMG-альтернатор промышленного класса
A.R.K5E предназначен для непрерывной и резервной работы, обеспечивая чистую и стабильную генерацию энергии с высокой надёжностью и эффективностью.
[rank_math_breadcrumb]
A.R.K5E предназначен для непрерывной и резервной работы, обеспечивая чистую и стабильную генерацию энергии с высокой надёжностью и эффективностью.
Electrical Performance
Type: Three-phase, brushless, self-excited synchronous alternator with PMG excitation
Frequency: 50 / 60 Hz
Power Factor: 0.8
Voltage Range: 380/220V – 480/277V (reconnectable in star, delta, or parallel configurations)
Voltage Regulation: ±1.0%
Total Harmonic Distortion (THD): <5.0% (balanced load), <1.5% (no load)
Sustained Short Circuit Current: >300% rated current for 10 seconds
Efficiency: Up to 95.3% at full load
Overload Capacity: 110% for one hour in a six-hour cycle
Telephone Harmonic Factor (THF): <2%
Telephone Interference Factor (TIF): <50
Short Circuit Ratio (1/Xd): 0.09 typical
Reactances (Per Unit at Rated kVA):
Xd (Synchronous): 2.83–3.53
X’d (Transient): 0.12–0.17
X’’d (Subtransient): 0.09–0.12
Xq (Quadrature): 2.21–2.82
X’’q (Quadrature Subtransient): 0.24–0.34
X₂ (Negative Sequence): 0.16–0.23
X₀ (Zero Sequence): 0.06–0.10
Time Constants:
Transient (T’d): 0.08 s
Subtransient (T’’d): 0.012 s
Armature (Ta): 0.019 s
Open Circuit Field (T’do): 2.5 s
Waveform Distortion: <1.5% (no load), <5% (balanced linear load)
Sustained Short Circuit: 300% of rated current for 10 seconds
Construction & Design
Insulation Class: H (125°C rise at 40°C ambient)
Protection: IP23 (optional IP44 with derating)
Cooling: Self-ventilated air cooling (1.035 m³/s @50Hz, 1.312 m³/s @60Hz)
Frame: Rigid steel structure with cast aluminum front and rear covers
Winding: Double-layer stator winding, 2/3 pitch design eliminates triple harmonics
Rotor: Damped rotor with dynamic balancing to BS6861 standards
Bearings:
Drive End: 6220-2RS (sealed-for-life ball bearing)
Non-Drive End: 6314-2RS (sealed-for-life ball bearing)
Overspeed Capability: 120% of rated speed (2250 rpm)
Leads: 12 reconnectable leads for flexible configuration (star/delta/parallel star)
Inertia (WR²): 8.98 kg·m² (single bearing) / 8.70 kg·m² (double bearing)
Weight:
Rotor: 617 kg (single bearing) / 588 kg (double bearing)
Stator: 722 kg
Complete Alternator: 1543 kg (single bearing) / 1535 kg (double bearing)
Shipping Weight: 1635 kg (50Hz) / 1625 kg (60Hz)
Packing Dimensions: 166 × 87 × 124 cm
Regulation & Control
Excitation System: PMG excitation with brushless AVR control
AVR Model: MX341 (standard), optional SX460, SX440, AS440, MX321
Voltage Regulation Accuracy: ±1.0%
Parallel Operation: Supported with compatible AVR
Protection Features:
Stator winding and bearing overheat protection
Anti-condensation heater (optional)
RFI Suppression: BS EN 61000-6-2, BS EN 61000-6-4, VDE 0875G/N compliant
Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359
Certification: ISO9001 Quality Management System
Environmental Parameters
Operating Temperature: –15°C to +40°C
Relative Humidity: Up to 95% (non-condensing)
Altitude: Up to 1000 m without derating
Cooling Air Requirement: 1.035 m³/s (50Hz), 1.312 m³/s (60Hz)
Noise & Vibration: Balanced per BS6861 mechanical standards
Performance Summary
Efficiency Range: 94.5–95.3%
Voltage Dip (Transient Load): ≤25% at 0.8 PF
Recovery Time: <0.5 seconds
Locked Rotor Motor Starting: >300% of rated current
Applications: Prime power, standby, telecom, rental, mobile, refrigeration, lighting tower, and railway generator systems