[rank_math_breadcrumb]

Alternator A.R.K184H

A.R.K184H Alternator – Premium Brushless Alternator for Industrial and Standby Power Systems

The A.R.K184H alternator, developed by Arken Power Solutions, is a robust and efficient three-phase brushless synchronous alternator designed for demanding industrial, rental, and standby power applications. Featuring a self-excited AVR-regulated system (standard SX460, optional SX440 or MX341), it ensures ±1% voltage regulation, low harmonic distortion (<5% THD), and efficiency up to 87.7%. Built with Class H insulation, IP23 protection, and sealed-for-life ball bearings, this alternator offers outstanding mechanical strength, stable performance, and long operational life. Fully compliant with IEC60034, BS5000, NEMA MG1-22, and ISO9001 standards, it delivers consistent and clean power for continuous and emergency applications.

Alternator Model

A.R.K184H

50Hz (kVA)

37.5

60Hz (kVA)

46.9
Control SystemSELF EXCITED
A.V.R. OPTIONAL SX440
Voltage Regulation ± 1.0 %
Sustained Short Circuit>300% OF RATED CURRENT
Rated Power Factor0.8

Electrical Performance

  • Type: Three-phase, brushless, self-excited synchronous alternator

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 190–480 V (configurable for star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced linear load), <1.5% (no-load)

  • Sustained Short Circuit Current: >300% of rated current

  • Efficiency: Up to 87.7% (depending on frequency and voltage)

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Excitation System: Self-excited, AVR-controlled

  • AVR Models: SX460 (standard), SX440 / MX341 / MX321 optional

  • Short Circuit Ratio (1/Xd): 6.0 typical

Reactances (Per Unit, Saturated)

  • Xd (Synchronous): 1.858–2.515

  • X’d (Transient): 0.141–0.191

  • X’’d (Subtransient): 0.077–0.104

  • Xq (Quadrature): 0.898–1.216

  • X’’q (Quadrature Subtransient): 0.157–0.213

  • X₂ (Negative Sequence): 0.118–0.160

  • X₀ (Zero Sequence): 0.028–0.038

  • Leakage Reactance (XL): 0.058–0.078

  • Time Constants:

    • Transient (T’d): 0.024 s

    • Subtransient (T’’d): 0.015 s

    • Open Circuit Field (T’do): 0.57 s

    • Armature (Ta): 0.010 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with 5–10% derating)

  • Cooling: Self-ventilated air cooling

    • 50 Hz: 0.15 m³/s (318 cfm)

    • 60 Hz: 0.19 m³/s (403 cfm)

  • Frame: Steel structure with cast aluminum front and rear covers

  • Stator: Double-layer winding, 2/3 pitch eliminates triple harmonics

  • Rotor: Damped cage rotor, dynamically balanced to BS6861 standards

  • Bearings:

    • Drive End: 6309-2RS (ISO standard, sealed-for-life)

    • Non-Drive End: 6306-2RS (ISO standard, sealed-for-life)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads (series star, parallel star, or delta)

  • Stator Resistance: 0.1713 Ω/phase (22°C, series star connection)

  • Rotor Resistance: 0.89 Ω (22°C)

  • Rotor Inertia (WR²): 0.2763 kg·m² (single bearing), 0.2706 kg·m² (double bearing)

Dimensions & Weight

  • Wound Rotor Weight: 72.33 kg (single bearing) / 69.12 kg (double bearing)

  • Stator Weight: 73 kg

  • Complete Alternator Weight: 216 kg (single bearing) / 203 kg (double bearing)

  • Shipping Weight: 226 kg (single bearing) / 213 kg (double bearing)

  • Packing Dimensions: 84 × 59 × 75 cm

Regulation & Control

  • Excitation: Self-excited, AVR-controlled

  • AVR Model: SX460 (standard), SX440 / MX341 / MX321 optional

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (with compatible AVR)

  • RFI Suppression: BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N compliant

  • Standards Compliance: IEC60034, GB755, BS5000, VDE0530, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 0.15–0.19 m³/s depending on frequency

  • Noise & Vibration: Balanced per BS6861 mechanical standards

Performance Summary

  • Efficiency Range: 86.9–87.7%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, rental, telecom, mobile, lighting tower, refrigeration, and railway generator systems

Datasheet

Related Products